Permit Number: T12CM07417
Parcel: 10602248A

Address:
3710 N ORACLE RD

Review Status: Active

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM07417
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
Review Date Reviewer's Name Type of Review Description Status Comments
01/28/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
01/28/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify how the infrared heater (IH-1) is to be mounted under the low canopy with a recommended distance of 14-feet from the floor to the bottom of the radiant tube with the top of the canopy beam at only 111" (9'-3"). The manufacturer's minimum distance from the floor to the bottom of the radiant tube is 12-feet. [Original comment: Show the mounting heights for the two types of radiant heaters and include the manufacturer's minimum required clearances to the floor and to combustible construction materials.]

Final Status

Task End Date Reviewer's Name Type of Review Description
01/28/2013 ANY REJECT SHELF RECEIVED