Permit Review Detail
Review Status: Active
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM07417
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Active
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/28/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 01/28/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify how the infrared heater (IH-1) is to be mounted under the low canopy with a recommended distance of 14-feet from the floor to the bottom of the radiant tube with the top of the canopy beam at only 111" (9'-3"). The manufacturer's minimum distance from the floor to the bottom of the radiant tube is 12-feet. [Original comment: Show the mounting heights for the two types of radiant heaters and include the manufacturer's minimum required clearances to the floor and to combustible construction materials.] |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/28/2013 | ANY | REJECT SHELF | RECEIVED |