Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM07417
Parcel: 10602248A

Address:
3710 N ORACLE RD

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM07417
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
12/11/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
12/11/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Coordinate the gas piping design shown on P1.0 with detail A/P2.0. Show the pipe stub for the future kitchen if the stub is to be installed as part of this activity and indicate your basis for sizing the stub. Reference: Sections 1211.9 and 1216.1, UPC 2006.
2. Verify the input for the radiant heaters (e.g. the Ambirad VPLUS 40 is shown as having an input of 41,500 BTUH).
3. Show that the installation of the flexible gas line complies with the manufacturer's requirements for stress relief.
4. Show how the new roofs are to be drained. Reference: Section 1101.11.1, UPC 2006.
12/11/2012 KEN BROUILLETTE FIRE REVIEW Approv-Cond Exiting will be evaluated by the fire inspector at time of final inspection. All exits including gates shall comply with the 2006 IFC.
12/11/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the mounting heights for the two types of radiant heaters and include the manufacturer's minimum required clearances to the floor and to combustible construction materials.
2. Clarify the venting of the specified low-intensity radiant heater, IH-1; the manufacturer's data shows a maximum length of 20 feet for the VPLUS 40.
12/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/18/2012 LOREN MAKUS ENGINEERING REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/20/2012 CPIERCE1 REJECT SHELF Completed