Permit Number: T12CM07398
Parcel: 141186320

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM07398
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. Please provide structural calculations and details for the following:
a. OK
b. Flag Pole foundation
NON-RESPONSIVE-PLEASE PROVIDE STRUCTURAL CALCULATIONS FOR THE FLAG POLE FOUNDATION

c. OK

2. For the structural calculations please provide foundation and roof framing key plans.
NON-RESPONSIVE - PLEASE PROVIDE VERTICAL DESIGN FOUNDATION AND FRAMING KEY PLANS IN THE CALCS.

3. OK
END OF REVIEW
02/01/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
02/01/2013 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; see items #3 and #4 of the manufacturer's installation instructions. Both items require the structural engineer or architect to determine the structural integrity of the building structure or if the building structure requires modification to support the hood system. In addition to the total weight of the hood system, Section 507.6 requires the weight of personnel working on the hood to be included in the structural calculations. [Original comment: Provide structural calculations and details to show that the two Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.]
02/05/2013 PAUL MACHADO ENGINEERING REVIEW Denied The building plans cannot be approved prior the approval of the Grading Plan. The Grading plans have been submitted for review on 02-04-2013. PM.
02/14/2013 CPIERCE1 WWM REVIEW Denied NEED IWC REVIEW AND APPROVAL - 724-6200
NEED TYPE III CAPACITY REVIEW & APPROVAL - 740-6534
G.T.KOZIAL 2/14/13

Final Status

Task End Date Reviewer's Name Type of Review Description
03/01/2013 CPIERCE1 REJECT SHELF Completed