Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/28/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | 1. Please provide structural calculations and details for the following: a. All wall mounter water heaters. Please identify each specific water herater. b. Flag Pole foundation c. Masonry screen wall, fencing and gates 2. For the structural calculations please provide foundation and roof framing key plans. 3. Please verify validity of additional special inspections added in the Conditions menu of this permit application. END OF REVIEW |
12/04/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Clarify the connected load for the natural gas system; on sheet P1 it is 7,604 CFH but on sheet P6 it is 6,694 CFH. Reference: Section 106.3.1, IPC 2006. 2. Detail 4/M2 shows the connection for a gas-fired radiant heater; where does the appliance show on the plans. If it is part of this activity, revise the gas piping accordingly. Reference: Section 106.3.1, IPC 2006. 3. An approved 2-way cleanout fitting is a single fitting, not a field-assembled group of individual fittings as shown in detail 2/GP-2. Reference: Sections 708.3.5 and 708.5, IPC 2006. 4. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Section 802.1, IPC 2006. 5. Revise the size of the vents for the combination drain and vent systems located roughly along column lines E and G; vents exceeding 40-feet in developed length are required to be increased by one pipe size for their entire length. Reference: sections 912.2.3 and 916.2, IPC 2006. |
12/04/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
12/05/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Provide keynote 15.705, noted on sheet M2. Reference: Section 106.3.1, IMC 2006. 2. Show the size, routing, and termination of the condensate drain for RTU-19. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson. 3. Revise the size of the condensate drains. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson. 4. Provide calculations to show that the proposed ventilation system will result in the maximum concentration of contaminants in the building not exceeding the concentration obtained by using the ventilation system based on Section 403.3, IMC 2006 or ASHRAE Standard 62.1-2004. Reference: Section 403.2 (exception) and Section 403.3, IMC 2006, as amended by the City of Tucson; see also, Section 6.3.2, ASHRAE Standard 62.1-2004 for documentation requirements. 5. Provide structural calculations and details to show that the two Type I hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006. |
12/06/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
12/07/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
12/10/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
12/17/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Denied | The building plans cannot be approved prior the approval of the Grading Plan. PM. 12-17-2012. |
12/24/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: WALMART 2: NEED DP APPROVAL - CHAD AMATEAU-740-6547 2: NEED TO SHOW LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER WITH BUILDING PERMIT DRAWINGS - (MAY NEED ADDITIONAL PERMITS FOR PRIVATE SEWER WITH DEQ REVIEW AND/OR PUBLIC SEWER) 4: NEED CAPACITY EVALUATION - PCRWRD/3RD FLOOR/KURT STEMM - 740-6534 5: NEED WASTEWATER/IWC/"RUSTY" REVIEW OF GREASE INTERCEPTORS - 520-724-6200- 3035 W EL CAMINO DEL CERRO 6: NEED TO SHOW SIZE AND LOCATION OF ALL WATER METERS ON THE PROPERTY FOR SEWER CONNECTION FEE CALCULATION |