Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07396
Parcel: 12510003G

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07396
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2013 SPOWELL1 WWM REVIEW Needs Review
11/20/2012 STEVE SHIELDS ZONING REVIEW Approved
11/20/2012 LOREN MAKUS ENGINEERING REVIEW Approved
11/20/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/20/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET P2; PLUMBING PLAN NOTE 2: THE NOTE INDICATES THE HOT WATER HEATER SUPPORT SHELF REQUIREMENTS WILL BE SHOWN ON THE ARCHITECTURAL PLANS. NO DETAIL WAS FOUND. PROVIDE.
11/20/2012 ERIC NEWCOMB ADA REVIEW Passed
11/21/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. even when the lights are off in the restrooms). Reference: Section 403.2.1 (4), IMC 2006.
11/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The existing shell building has a 3/4" water service, either the 1-1/4" service proposed on P2 needs to be revised or the water service must be changed.
2. Provide cleanouts sized no smaller than required by Section 707.11, UPC 2006 (e.g. provide a 4" cleanout for the 4" drain in the men's restroom).
3. Horizontal drain lines serving sinks require cleanouts. Reference: Section 707.4, UPC 2006.
4. Show how the water temperature for the lavatories is to be limited to 11 degrees Fahrenheit. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
5. Provide information to show how the proposed water heater is to be supported from the building structure (no details provided on the architectural drawings). Reference: Section 314.5, UPC 2006.
11/21/2012 ROBERT SHERRY WATER REVIEW Approved
11/21/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07396
1. Main Disconnect requires a neutral per 250.24(C)
2.Mechanical Plans examiner requires ex-fans in restrooms to come on when air is supplied to restroom by unit not just when light is on.
3.The 2/0 copper feeders to the transformer should be procted at 175 amps per 240.6.(On one line diagram)
4.0Sheet E.2 shows the transformer in front of the panels, in the clearance area reqyuired by the panels.
5. Show location of the landlords Main Service.
6. Provide an existing load on the landlords service then add this space load for a new total,

Ray T Majuta
Elect Plan Review
DPSD, C of Tucson
11/21/2012
Ray.majuta@tucsonaz.gov.
11/26/2012 CARL SCHULTZ FIRE REVIEW Approved