Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM07327
Parcel: 12810078E

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07327
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
02/12/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Completed
11/21/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET A2.0
1. Please provide a second exit for conference room 212 as required by the 2006 IBC, Section 1019.1 with an occupancy load exceeding 50.
SHEET S1.1
2. Please provide certification of the special inspectors as required by specifications.
END OF REVIEW
11/29/2012 ROBERT SHERRY WATER REVIEW Approved
11/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a design for the exhaust for the batteries in the UPS room complies with the requirements of Section 502.4, IMC 2006.
11/30/2012 MARTIN BROWN FIRE REVIEW Approved
12/04/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/04/2012 CPIERCE1 APPROVAL SHELF Completed