Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07327
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/12/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Completed | |
| 11/21/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A2.0 1. Please provide a second exit for conference room 212 as required by the 2006 IBC, Section 1019.1 with an occupancy load exceeding 50. SHEET S1.1 2. Please provide certification of the special inspectors as required by specifications. END OF REVIEW |
| 11/29/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/29/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/29/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Provide a design for the exhaust for the batteries in the UPS room complies with the requirements of Section 502.4, IMC 2006. |
| 11/30/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 12/04/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 12/04/2012 | CPIERCE1 | APPROVAL SHELF | Completed |