Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL - TI ALL
Permit Number - T12CM07304
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 02/13/2013 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 02/13/2013 | ROBERT SHERRY | WATER | REVIEW | Denied | Comment not addressed. Indicate the size of the water meter (shown as existing on the civil plans) and the required reduced pressure backflow prevention assembly to be installed |
| 02/13/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 02/13/2013 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 02/13/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | Revise the roof drainage calculations. A gutter is not a horizontal pipe; use Table 11-3, UPC 2006 to determine the required size of the gutter, using the roof area served by each section of gutter (i.e. if the gutter has three equally-spaced downspouts, divide the roof area by three) and show the slope of the gutters on the plans. [Second comment: Clarify the intent for roof drainage; the roof plan and some of the details and calculations indicate the use of four scuppers in a parapet wall but other drawings show a gutter along the north wall and no parapet. In neither case are the calculations compliant to the 2006 UPC. To size a gutter, see Table 11-3; to size the downspouts for a gutter, use Table 11-1, UPC 2006. If the roof design is changed to require scuppers, see Section 1101.11.2.1, 2006 UPC which directs you to set the scupper width equal to the circumference of the required roof drain from Table 11-1, UPC 2006. With scuppers or roof drains, overflow capability is required per Section 1101.11.2.2, UPC 2006.] [Original comment: Revise the roof drain sizing based at a minimum, on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour per the requirements of the Uniform Plumbing Code. Reference: Section 1101.11.1 and Table 11-1, UPC 2006.] |
| 02/14/2013 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: AUTO ZONE 2: NEED TO IDENTIFY SIZE & SERIAL NUMBER OF EXISTING WATER METER ON DRAWINGS AND VERIFY PAYMENT OF SEWER USER FEES FOR SEWER CONNECTION FEE EVAL/CALC |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 02/22/2013 | CPIERCE1 | REJECT SHELF | Completed |