| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/21/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/21/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Denied | Development Package must be approved first. |
| 11/29/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Denied | SHEET A-1 1. Provide a section reference to detail 2/A4. SHEET A4 2. At detail 7: a. Show all required accessible clearances for toilet, lavatory, door and water dispensers. b. Show required dimension from wall to center line of water closet. 3. At detail 6: a. Show water closet required height dimension b. Show required height of water dispenser spouts c. Delete all references to ADA and insert ICC A117.1 SHEET CO.1 4. The light pole base depth shown on detail 13 does not correlate with structural calculations. Please reconcile and resubmit. END OF REVIEW |
| 12/05/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | 1. Reduced pressure backflow prevention assemblies are required to be installed in locations accessible to Tucson Water. Reference: Chapter XXVII, Article V, Section 27-72, the Tucson Code, http://cms3.tucsonaz.gov/sites/default/files/water/docs/backflow-ordinance.pdf 2. Indicate the size of the water meter (shown as existing on the civil plans) and the required reduced pressure backflow prevention assembly to be installed. |
| 12/05/2012 | DAVID RIVERA | ZONING | REVIEW | Denied | Zoning has reviewed the building plan for compliance with the development package plans. While the building plans are in substantial compliance with the un-approved version of the development package site plan as it pertains to the zoning review purview, zoning cannot approve them until such time as the development package is approved. |
| 12/06/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Verify the model number of the specified rooftop units. The energy code analysis (COMcheck) calls out a gas-fired unit but the model number of the scheduled unit does not appear in Carrier's on-line catalog. Reference: Section 106.3.1, IMC 2006. |
| 12/06/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Revise the roof drain sizing based at a minimum, on a storm of 60-minutes duration and a 100-year return period, i.e. 3" per hour per the requirements of the Uniform Plumbing Code. Reference: Section 1101.11.1 and Table 11-1, UPC 2006. 2. Clarify the installation of the hot water temperature control valves for the lavatories. The installation shall comply with the manufacturer's listing requirements (i.e. the valve is to be located at or near the water heater; ASSE 1016 or ASSE 1070 listed devices are required at fixtures for scalding protection). Reference: Section 310.4, UPC 2006. 3. Provide the type of backflow preventer to be used between the yard water hydrant and the water distribution system. Reference: Sections 103.2.3 and 603.1, UPC 2006. 4. Clarify the proposed water closet; the Kohler K-3575 water closet is not accessible and is not a "Highline" model. Reference: Section 103.2.3, UPC 2006. |
| 12/14/2012 | GERRY KOZIOL | WWM | REVIEW | Denied | 1: AUTO ZONE 2: NEED TO IDENTIFY SIZE & NUMBER OF EXISTING WATER METER ON DRAWINGS AND VERIFY PAYMENT OF SEWER USER FEES FOR SEWER CONNECTION FEE EVALUATION CALCULATION |
| 12/17/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07304 8825 E Broadway Bl New Auto Zone 1. Provide a location on the electrical sheets showing the 600 Amp Main Service. 2. Concerning the Fault Current at the service, the Utility Co in their Service Requirement Book for this area shows a Fault Current of 55,600 amps at the Utility transformer, describe how the 42,000 amp rating for service equipment was arrived at. 3.The note regarding The Series Rated system of 42,000 AIC on sheet E-4, should also state that it is to be a 42K AIC /10 K AIC Rated System. 4. The City of Tucson has an Outdoor Lighting Code ( Ord # 10963) which requires compliance through a calculation. This ordinance can be obtained on City's website by going to Departments, Development Services, Codes, Building Codes and to the ordinance.(For both site and building lighting) 5. Show where the site lighting is to go, provide spec's sheets for the fixtures, and assign circuit numbers to them, show on electrical sheets. 6. Show where the signs are located, assign circuits to them, show on electrical sheets. Ray T Majuta Elect Plan Review PDSD, City of Tucson 12/17/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/17/2013 | CPIERCE1 | REJECT SHELF | Completed |