Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07287
Parcel: 105110700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07287
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/27/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Include the pressure drop from the double check valve in the water pressure calculations. [Original comment: Clarify the purpose of the double check valve on the water service to the suite; the accessible backflow preventer (RP) is located outside of the building, by the water meter.]
2. General Note 4 on sheet P-1 calls for all backflow preventers to be located above the dropped ceiling. [Original comment: Relocate the reduced pressure backflow preventers to conform to the access and clearance requirements of Section 603.3.4, UPC 2006.]
3. Detail 1/P-2 shows all three compartments being indirectly wasted. [Original comment: Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006.]
4. Revise the size of the water supply to the flush valves for the water closets; the flush valve has a flow requirement of approximately 25 GPM which will result in a water velocity in excess of 8 FPS.
11/27/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Comment not resolved; Table 403.3, IMC 2006 requires 100 people per 1,000 square feet. [Original comment: The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2006 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2006.]
11/30/2012 FRODRIG2 WWM REVIEW Needs Review
11/30/2012 FRODRIG2 ZONING REVIEW Needs Review
11/30/2012 FRODRIG2 FIRE REVIEW Needs Review