Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07287
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/15/2012 | MICHAEL ST. PAUL | ZONING | REVIEW | Denied | Depict outdoor seating on all floor plans, and confirm parking calculations for all dinning areas. (See D06-0014.) |
11/15/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Show the size, routing, and termination of the condensate drains; condensate may not terminate onto the roof. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson and Section 814.0, UPC 2006. 3. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006. 4. The occupant load used to calculate the required ventilation is not necessarily the same as the occupant load used for calculating exiting requirements. The occupant load used for calculating the minimum required ventilation is to be based on Table 403.3, IMC 2006 or an approved engineering analysis of the specific occupancy type. Reference: Section 403.3, IMC 2006. 5. Coordinate the air balance schedule on sheet M-2 with the mechanical plan; the mechanical plan shows 50 CFM being supplied to each restroom. |
11/15/2012 | LEERAY HANLY | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/15/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/15/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T-1; BUILDING CODE DESIGN DATA: REVISE THE OCCUPANCY TYPE FROM A 'B' TO AN 'A2' (RESTAURANT). 2. SHEET A-1.1; DETAIL 2: ON THE DIAGONAL BRACE, PROVIDE A CONNECTOR SIZE AND QUANTITY AT THE WALL AND ROOF. 3. SHEET A-1.1; DETAIL 8: COORDINATE THE OVER FLOW PIPE SIZE WITH THAT SHOWN ON THE MECHANICAL DRAWINGS. 4. SHEET A-3; FINISH SCHEDULE: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 5. SHEET A-4; FIRE RESISTANCE RATINGS: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 6. SHEET A-9; SECTION 2C: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE. 7. GENERAL: PROVIDE A SITE PLAN AS REQUIRED PER THE IBC SECTION 106.2. 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
11/15/2012 | PAUL MACHADO | ENGINEERING | REVIEW | Approved | |
11/15/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Section R4-30-304 of the Rules of the Arizona State Board of Technical Registration, states that a notation shall be placed beneath the seal, either written, typed, or electronically generated, that provides the day, month, and year of the expiration of current registration. (Effective March 8, 2008). 2. Clarify the purpose of the double check valve on the water service to the suite; the accessible backflow preventer (RP) is located outside of the building, by the water meter. 3. Relocate the reduced pressure backflow preventers to conform to the access and clearance requirements of Section 603.3.4, UPC 2006. 4. A double check valve is not acceptable for protecting the water supply to a carbonator. Reference: Section 603.4.12, UPC 2006. 5. Provide water pressure and water pipe sizing calculations. Reference: Section 610.1, UPC 2006. 6. Provide upper terminal cleanouts on horizontal drainage pipes exceeding 5 feet in length (horizontal drain lines serving sinks require cleanouts regardless of length). Reference: Section 707.4, UPC 2006. 7. Provide a direct waste connection for the wash and rinse sections of the 3-compartment sink, with an indirect connection for the sanitizing compartment only. Reference: Sections 304.0, 704.3, and 801.2.3, UPC 2006. 8. Detail 2/P-2 shows a vent offsetting below the flood rim of the fixture it serves. Each vent pipe shall rise vertically to a minimum of 6" above the flood-level rim of the fixture it serves before offsetting horizontally. Reference: Section 905.3, UPC 2006. |
11/15/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
11/15/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
11/27/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
11/27/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review |