Permit Number: T12CM07258
Parcel: 12801005H

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07258
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/14/2012 MARTIN BROWN FIRE REVIEW Approved
11/14/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
11/14/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/14/2012 ROBERT SHERRY WATER REVIEW Approved
11/14/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1; SITE PLAN: SITE KEYNOTE 111 WAS NOT FOUND ON THE PLAN. VERIFY.
2. SHEET A1; SITE PLAN: SITE KEYNOTE 117 IS ON THE PLAN, BUT WAS NOT LISTED IN THE SITE KEYNOTES. VERIFY.
3. SHEET A2; SITE PLAN: KEYNOTE 3 WAS NOT FOUND ON THE PLAN. VERIFY.
4. SHEET A3 (SECTION 2); STRUCTURAL CALCULATIONS (SHEET 3): THE CALCULATIONS INDICATE A 12" THICK CONCRETE SLAB DESIGN, WHILE THE DETAIL INDICATES A 6" PAD. CLARIFY.
5. GENERAL: PROVIDE MATERIAL STRENGTHS ON THE DRAWINGS (MASONRY, CONCRETE, GROUT, REINFORCING, ETC.).
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/14/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Passed
11/14/2012 ERIC NEWCOMB ADA REVIEW Passed
11/14/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/15/2012 CPIERCE1 WWM REVIEW Needs Review
11/15/2012 STEVE SHIELDS ZONING REVIEW Approved
11/15/2012 LOREN MAKUS ENGINEERING REVIEW Approved