Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07258
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/14/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
11/14/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
11/14/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
11/14/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
11/14/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1; SITE PLAN: SITE KEYNOTE 111 WAS NOT FOUND ON THE PLAN. VERIFY. 2. SHEET A1; SITE PLAN: SITE KEYNOTE 117 IS ON THE PLAN, BUT WAS NOT LISTED IN THE SITE KEYNOTES. VERIFY. 3. SHEET A2; SITE PLAN: KEYNOTE 3 WAS NOT FOUND ON THE PLAN. VERIFY. 4. SHEET A3 (SECTION 2); STRUCTURAL CALCULATIONS (SHEET 3): THE CALCULATIONS INDICATE A 12" THICK CONCRETE SLAB DESIGN, WHILE THE DETAIL INDICATES A 6" PAD. CLARIFY. 5. GENERAL: PROVIDE MATERIAL STRENGTHS ON THE DRAWINGS (MASONRY, CONCRETE, GROUT, REINFORCING, ETC.). 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
11/14/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Passed | |
11/14/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
11/14/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
11/15/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
11/15/2012 | STEVE SHIELDS | ZONING | REVIEW | Approved | |
11/15/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved |