Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM07253
Parcel: 116240800

Address:
20 S PANORAMA CI

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM07253
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/07/2013 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Denied T12CM07253
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, highlighting any changes, along with a written response to each of the notated items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2006 International Residential Code, 2006 International Energy Conservation Code, and Arizona State amendments to the 2006 Uniform Plumbing Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

FLOOR PLANS:

1. Show compliance with R303.1 providing (4%) natural ventilation into the new rooms, or mechanical ventilation with fresh air provision.
2. Show compliance with R310 providing egress from the bedroom by meeting the 20" minimum width requirement.

SECTIONS - DETAILS:

1. Clarify the 2 x 12 @16" O.C. rafters, roof deck and covering as "replace with …" on sheet S2.0, R106.1.1. Keynote #16 sheets A1.0 And A1.1 shows replacement, but sheet S2.0 does not indicate the materials and sizes for the new roof.

MECHANICAL PLANS:

1. Provide return air duct and register sizes meeting minimum requirements of 72 SQ IN/ ton, M1403. Minimum duct/register size: heat pump or air conditioner - 6 SQ IN per 1,000 BTU (1 ton cooling = 12,000 BTU). The 1.5 ton unit requires a minimum 108 square inch return air duct.

ELECTRICAL PLANS:

1. Show locations of interconnected smoke alarms at each floor level, R313.

If you have any questions please contact:
Ken Van Karsen
(520) 837-4912
City of Tucson Residential Plan Review
01/10/2013 KEN BROUILLETTE FIRE REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
01/17/2013 SHANAE POWELL OUT TO CUSTOMER Completed