Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM07221
Parcel: 115070680

Address:
210 W ELM ST

Review Status: Completed

Review Details: COMMERCIAL - NEW

Permit Number - T12CM07221
Review Name: COMMERCIAL - NEW
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2012 MARTIN BROWN FIRE REVIEW Approved
11/16/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. The 2006 IBC, Section 2902.2, Exception 2, requires separate toilets with an occupancy load of 16 or more. Please add another accessible toilet room.
a. Also, need to provide a water dispenser and a service sink.
2. Certification of special inspector forms required the name of the actual inspector that is selected to preform the inspections, not the name of the firm he/she is employed
3. COT lettering size standards is 3/32" (actual lettering size not font size) minimum both upper and lower case. Please have your structural engineer change all the non-compliant letter sizes on his sheets and resubmit.

T12CM07221
STRUCTURAL REVIEW COMMENTS

4. SHEET S1.1; GENERAL STRUCTURAL NOTES: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE SHEET.
5. SHEET S1.2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE SHEET.
6. SHEET S2.1 (FOUNDATION PLAN); STRUCTURAL CALCULATIONS: THE FOOTINGS MARKED F5 ON THE FOUNDATION PLAN AT THE MECHANICAL PLATFORM WERE NOT FOUND IN THE CALCULATIONS. VERIFY.
7. SHEET S2.2 (FLOOR PLAN); FRAMING NOTES: NOTE 9 INDICATES MASONRY CONTROL JOINTS ARE SHOWN ON THE PLAN. PROVIDE.
8. SHEET S3.1; FOUNDATION DETAILS: THIS SHEET WAS NOT INCLUDED IN THE REVIEW SET DRAWINGS. PROVIDE.
9. STRUCTURAL CALCULATIONS; SHEETS D1 THROUGH D5: WHERE DO THESE WALL SHOW UP ON THE DRAWINGS? VERIFY.
10. GENERAL: PROVIDE THE NORTH ARROW ON ALL PLANS.
11. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
END OF REVIEW
11/28/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. The roof drainage calculations are based the 2006 IPC but the Applicable Code notes on sheet 1 of 13 refer to the 2006 UPC. This review has been made using the 2006 UPC.
2. Provide the minimum plumbing facilities required by Table 2902.1 and Section 2902.2, IBC 2006, for a business occupancy. See also, Section 1109.5.1, IBC 2006.
3. Revise the specification for the underground water distribution pipe from Type M to Type L Copper. Reference: Section 604.2, UPC 2006.
4. Revise the size of the provided scuppers to comply with the requirements of Section 1101.11.2.1, UPC 2006. Provide overflow protection for the roof. Refer also to Section 1106.4, UPC 2006.
11/28/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Show the size, routing, and termination of the condensate drain for the new air handler. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson.
2. Verify that the space allocated to the two condensing units is adequate to provide the maintenance clearance specified by the manufacturer. Reference: Sections 304.1 and 306.1, IMC 2006.
11/28/2012 ROBERT SHERRY WATER REVIEW Approved
12/04/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
12/04/2012 STEVE SHIELDS ZONING REVIEW Denied PDSD TRANSMITTAL

FROM: Steve Shields
Lead Planner

PROJECT: Sentinel Peak Brewing Company
T12CM07221
Building Plan (1st Review)

TRANSMITTAL DATE: December 4, 2012

1. The building plan has been reviewed by Zoning Review Section but cannot approve the plan until all zoning comments or concerns have been addressed.

2. Zoning can not approve the building plan until a development package has been approved by all PDSD agencies.

3. Zoning will re-review the building plan on the next submittal to insure compliance with the approved development package. Additional comments may be forthcoming.

If you have any questions about this transmittal, please contact me at Steve.Shields@tucsonaz.gov or (520) 837-4956
12/10/2012 GERRY KOZIOL WWM REVIEW Passed

Final Status

Task End Date Reviewer's Name Type of Review Description
12/13/2012 CPIERCE1 REJECT SHELF Completed