Permit Number: T12CM07167
Parcel: 13340001C

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM07167
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/14/2013 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07167
7570 E Speedway
Solar Photovoltaic System

1. The new 800 amp services ( twelve) will be required to have their grounding systems upgraded as well, cannot use existing, upgraded services require larger sized grounding systems, provide on plan snd show installation and compliance with NEC 250.

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
1/14/13