Review Details: RESUBMITTAL
Permit Number - T12CM07167
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2013 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM07167 7570 E Speedway Solar Photovoltaic System 1. The new 800 amp services ( twelve) will be required to have their grounding systems upgraded as well, cannot use existing, upgraded services require larger sized grounding systems, provide on plan snd show installation and compliance with NEC 250. Ray T Majuta Elect Plan Review PDSD, C of Tuc 1/14/13 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/17/2013 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 01/17/2013 | GERARDO BONILLA | REJECT SHELF | Completed |