Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM07167
Parcel: 13340001C

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM07167
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/21/2012 MARTIN BROWN FIRE REVIEW Approved
11/27/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET 1; GENERAL NOTES: NOTE 9 INDICATES A SOILS ENGINEER SHALL INSPECT AND TEST THE SOIL PREPARATION. WAS A GEOTECHNICAL INVESTIGATION REPORT PREPARED FOR THIS PROJECT? IF SO, PROVIDE THAT REPORT FOR REVIEW.
2. SHEET SD1: PROVIDE MATERIAL STRENGTHS ON THE DRAWINGS FOR THE WELDING.
3. STRUCTURAL CALCULATIONS: WHERE WERE THE VALUES USED IN THE CALCULATIONS FOR SOIL BEARING AND LATERAL RESISTANCE OBTAINED FROM? CLARIFY.
4. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
12/05/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM07167
7570 E Speedway
Photovoltaic System Installation
1. Per City of Tucson Commercial Plan Submittal Requirements, all text upper and lowercase to be minimun 3/32'', and to be clear and legible.The following sheets do not meet above requirements, E1.1, E1.3, E1.5, E1.7, E1.9, E1.11, E1.13, E1.15 and E1.16.
2. Provide manufactures specification sheets for the following seperately as well as what has be printed on the plans, spec's sheets for the inverters, panels and the combiner boxes.
3. Show on plans where the following are located:
Main Services MPB 1 through MPB 7,
Disconnects for ACDS 1-1 through ACDS 7-1
TEP Meters (PV)
CT Compartments
Transformers
Disconnects ACDS 1-2 through ACDS 7-2
AC Panelboards
Inverters/DC Combiner Boxes
(locations are required per C of Tuc Submittal Reqmt's)
4. Provide on plans a detail showing how the tap into supply side on main services is to be installed showing following:
a. compartment of Main Service to be entered,
b. are bus sections pre drilled or to be drilled?
c. type of terminations to be used on conductors
d. room for conductors in compartment ?
e. location of ACDS disconnects in relation to MPB's
f. detail of how section 690.47 is to be accomplished and
conductor size
if taps for each service is same as for all only one detail required, if taps different, detail for each required.
The concern for the supply side taps is due to the applicability of the MPB to receive the new conductors. once this is determined this Jurisdiction may require a 3rd party certification depending on how the MPB has to be arranged.
5. Detail how the transformers are to be grounded, show conductor size.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tuc
12/6/2012
Ray.Majuta@tucsonaz.gov

Final Status

Task End Date Reviewer's Name Type of Review Description
12/21/2012 FERNE RODRIGUEZ REJECT SHELF Completed