Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM07110
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/07/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET S1: PROVIDE MATERIAL STRENGTHS ON THE DRAWING. SEE SHEET 2 OF THE CALCULATIONS, INCLUDING SOIL BEARING. OMIT MATERIALS NOT USED ON THIS PROJECT.
2. SHEET S1: PROVIDE CALCULATIONS FOR THE ROOF DIAPHRAGM DESIGN, AND ADD A NOTE ON THE DRAWING FOR THE CONNECTION OF THE DECK TO THE PURLINS.
3. SHEET S1 (FRAMING PLAN); STRUCTURAL CALCULATIONS (SHEET 5): THE CALCULATIONS INDICATE JOISTS ARE TS 8X3X 1/4 AT 4'-6" O.C., WHILE THE PLAN INDICATES 8" GALVANIZED 14 GA. PURLINS AT 4'-6" O.C. CLARIFY.
4. SHEET S1: PROVIDE DESIGN LOADS ON THE DRAWING.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/07/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
11/19/2012 CAGUILA1 ENGINEERING REVIEW Needs Review
11/19/2012 CAGUILA1 FIRE REVIEW Needs Review
11/19/2012 CAGUILA1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/19/2012 CINDY AGUILAR OUT TO CUSTOMER Completed