Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM07102
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/07/2012 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 11/07/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 11/07/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 11/08/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 11/08/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/08/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/08/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL: PROVIDE A HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER PER IBC TABLE 2902.1. 2. GENERAL: PROVIDE A DETAIL FOR THE LATERAL BRACING OF INTERIOR PARTITIONS IN ORDER TO MEEET THE REQUIREMENTS OF IBC SECTION 1607.13. INCLUDE IN THE DETAILS THE BRACING MEMBER SIZE, SPACING, AND CONNECTION TO THE TOP OF THE PARTITION WALL AND TO THE STRUCTURAL FRAMING ABOVE. |
| 11/08/2012 | GERRY KOZIOL | WWM | REVIEW | Passed | |
| 11/08/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/08/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 11/08/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed |