Permit Number: T12CM07074
Parcel: 105110700

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM07074
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2012 STEVE SHIELDS ZONING REVIEW Approved
11/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Condensate drains may not terminate over a roof drain or gutter unless the roof drain or gutter terminates at or above grade in an area capable of absorbing the condensate flow without surface drainage. Reference: Section 307.2.1, IMC 2006, as amended by the City of Tucson.
2. Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted. Reference: Section 403.2.1 (4), IMC 2006.
3. Provide calculations demonstrating adequate ventilation. Reference: Section 403.3, IMC 2006, as amended by the City of Tucson.
11/06/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12cm07074

1. Show the location of the main electrical service on one of the electrical sheets.
2. Show the total existing load in amperage on the main service ( and how it was obtained ), then add this space for a combined total on building service.
3. Sheets E-5, 6 and 7 must be minimum 3/32" lettering, this is a City of Tucson Requirement for tenant improvements.

Ray T majuta
Electrical Plan Review
PDSD, City of Tucson
11/06/2012
Ray.Majuta@tucsonaz.gov
11/06/2012 ROBERT SHERRY WATER REVIEW Denied Provide a site drawing showing the size and route of the building water supply along with the location and size of both the water meter and the reduced pressure backflow preventer assembly. Reference: Section 103.2.3, UPC 2006.
11/06/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. COVER SHEET; DIVISION OF WORK: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
2. COVER SHEET: PROVIDE A SITE PLAN FOR THIS PROJECT PER THE IBC SECTION 106.2.
3. SHEET A1.2; FLOOR PLAN: PROVIDE AN ELEVATION IN BREAKROOM 108 INDICATING AN ACCESSIBLE SINK PER THE IBC SECTION 1109.3.
4. SHEET A1.2; PLUMBING SCHEDULE: PROVIDE A DETAIL (INCLUDING MEMBER SIZES AND CONNECTIONS) FOR THE ABOVE CEILING WATER HEATER.
5. SHEET A1.2; RESTROOM PLAN: REMOVE "FOR REFERENCE" FROM THE TITLE.
6. SHEET A6; PARTITION TYPES: PROVIDE DETAILS AT THE INTERIOR PARTITIONS THAT MEET THE IBC SECTION 1607.13 FOR LATERAL RESISTANCE. PROVIDE BRACE MEMBER SIZES, SPACING, AND CONNECTIONS TO THE TOP OF THE WALL AND TO THE STRUCTURE ABOVE.
7. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/06/2012 LOREN MAKUS ENGINEERING REVIEW Approved
11/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Revise the font size used on the drawings to a minimum of 3/32-inch (all upper case). Reference: Section 106.1.1, IBC 2006.
2. Provide a design for the mounting shelf for the water heater along with structural calculations to show that the water heater is safely supported. Reference: Sections 310.0 and 314.5, UPC 2006.
3. Show how the temperature of the hot water supply to the public lavatories is controlled. Reference: Section 413.1, UPC 2006 and Section 504.3, IECC 2006.
4. Provide calculations showing how the water supply piping has been sized. Reference: Sections 610.4 and 610.5, UPC 2006.
5. Verify that upper terminal cleanouts have been provided for the water closets. Reference: Section 707.4, UPC 2006.
6. Provide cleanouts sized per Section 707.11, UPC 2006.
7. Show the location of the existing building drain to which the new drain piping is to be connected. Reference: Section 103.2.3, UPC 2006.
11/06/2012 ERIC NEWCOMB ADA REVIEW Passed
11/06/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
11/07/2012 KEN BROUILLETTE FIRE REVIEW Approved
11/14/2012 GERRY KOZIOL WWM REVIEW Approved