Permit Number: T12CM07038
Parcel: 11302054M

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM07038
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/20/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 11-26-12
Activity: T12CM07038
Address: 1230 E Easy Street
Applicant: T12CM07038

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Insulation is not optional. Clarify note on detail #8 sheet 7.

PLUMBING PLAN:
2. Include a discharge to both the black water building drain and gray water for the proposed washing machine.
3. Note and specify all piping materials, UPC 301.1.1.
4. Specify water conservation requirements: Water closets = 1.6 gallons per flush, Sinks/ Showerheads = 3 gpm, UPC State Amend. 45-312.
5. Shower and tub/shower combinations that have individual control valves shall be of the pressure balance or thermostatic mixing valve type.
6. Provide note requiring that water hammer arrestors be installed in accordance with ASSE 1010-2004 on water lines serving appliances equipped with quick-closing valves to include but not limited to clothes washers, UPC 609.10.
7. All construction drawings submitted after March 1, 2009 for one- or two-family dwellings require a solar water heating system, or future installation preparation with one of the following provisions: control and ¾"water piping; 3" metallic sleeve; or an accessible attic over the water heater.

MECHANICAL PLAN:
8. Show supply and return air ducts with a minimum R-8 insulation when located outside the thermal envelope, R1103.2.1.
9. Provide a mechanical equipment specification list, M1302.1.

ELECTRICAL PLAN:
10. Bedroom outlets shall be protected with combination-type arc-fault breakers (receptacles, lights, and smoke detectors), E3802.12.
11. Convenience receptacles and light switches/fixtures shall be provided within 25' of mechanical equipment, E3801.11, E3803.4.
12. Exterior outlets at grade level shall be provided at both the front and back of the dwelling, E3801.7. These outlets shall be GFCI protected E3802.3.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review