Permit Number: T12CM06961
Parcel: 12709016A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06961
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2012 RONALD BROWN BUILDING-COMMERCIAL REVIEW Approved
11/29/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/29/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/29/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Clarify the sequence of operation for the exhaust fans. The note on sheet M-1 calls for the exhaust fans to be wired to the light switch with a delay timer and to be interlocked with RTU-5 but it doesn't clearly state when the fan is to operate. [Original comment: Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan remains on as long as air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006.]
12/21/2012 FRODRIG2 WWM REVIEW Needs Review
12/21/2012 MARTIN BROWN FIRE REVIEW Approved