Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06961
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 11/29/2012 | RONALD BROWN | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 11/29/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Approved | |
| 11/29/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/29/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Clarify the sequence of operation for the exhaust fans. The note on sheet M-1 calls for the exhaust fans to be wired to the light switch with a delay timer and to be interlocked with RTU-5 but it doesn't clearly state when the fan is to operate. [Original comment: Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan remains on as long as air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006.] |
| 12/21/2012 | FRODRIG2 | WWM | REVIEW | Needs Review | |
| 12/21/2012 | MARTIN BROWN | FIRE | REVIEW | Approved |