Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06961
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/31/2012 | DAVID RIVERA | ZONING | REVIEW | Approved | |
| 10/31/2012 | JASON GREEN | ENGINEERING | REVIEW | Approved | |
| 10/31/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Approved | |
| 10/31/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET T2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES AND RESPONSIBILITY CHART. 2. SHEET T2; CODE ANALYSIS: ADD THE ICC/ANSI A117.1-2003 CODE FOR ACCESSIBILITY TO THE PLANS. 3. SHEET FP1: A NOTE INDICATES "PRELIMINARY LAYOUT NOT FOR CONSTRUCTION". REVISE. 4. SHEET AS1: A NOTE INDICATES "FOR REFERENCE ONLY". REVISE. 5. SHEET A3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PLAN SECTION CUTS. 6. SHEET AS; DETAIL 1: TWO NOTES INDICATE TO "SEE PLAN" FOR THE STRUCTURAL COLUMN. SINCE COLUMNS ARE EXISTING, REMOVE THE NOTE AND LEAVE THE PART OF THE NOTE THAT INDICATES TO VERIFY THE SIZE OF THE COLUMN IN THE FIELD. 7. GENERAL: DARKEN THE DRAWINGS (PLANS AND ELEVATIONS). 8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/31/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 11/02/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan remains on as long as air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006. |
| 11/02/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006. 2. Verify the installation of the back-to-back water closets complies with Section 706.3, IPC 2006 with regard to the fittings. |
| 11/02/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 11/02/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM06961 5545 E Broadway #119 1. Provide 2006 IECC Budget Lighting calculation for the interior, ComCheck ok. 2.Provide a load for the Main Service which includes the load for this space. 3. Indicate on electrical plans where the main service located. Ray T Majuta Electrical Plan Review PDSD, C of Tuc 11/2/2012 Ray.majuta@tucsonaz.gov |
| 11/16/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 11/16/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review |