Permit Number: T12CM06961
Parcel: 12709016A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06961
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/31/2012 DAVID RIVERA ZONING REVIEW Approved
10/31/2012 JASON GREEN ENGINEERING REVIEW Approved
10/31/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
10/31/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET T2: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES AND RESPONSIBILITY CHART.
2. SHEET T2; CODE ANALYSIS: ADD THE ICC/ANSI A117.1-2003 CODE FOR ACCESSIBILITY TO THE PLANS.
3. SHEET FP1: A NOTE INDICATES "PRELIMINARY LAYOUT NOT FOR CONSTRUCTION". REVISE.
4. SHEET AS1: A NOTE INDICATES "FOR REFERENCE ONLY". REVISE.
5. SHEET A3: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE PLAN SECTION CUTS.
6. SHEET AS; DETAIL 1: TWO NOTES INDICATE TO "SEE PLAN" FOR THE STRUCTURAL COLUMN. SINCE COLUMNS ARE EXISTING, REMOVE THE NOTE AND LEAVE THE PART OF THE NOTE THAT INDICATES TO VERIFY THE SIZE OF THE COLUMN IN THE FIELD.
7. GENERAL: DARKEN THE DRAWINGS (PLANS AND ELEVATIONS).
8. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/31/2012 ERIC NEWCOMB ADA REVIEW Passed
11/02/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Revise the sequence of operation for the restroom exhaust fans so that all of the air supplied to the restrooms will be exhausted (i.e. the exhaust fan remains on as long as air is being introduced into the restroom). Reference: Section 403.2.1 (4), IMC 2006.
11/02/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide tempered water for the lavatories using approved devices conforming to ASSE 1070. Reference: Section 416.5, IPC 2006.
2. Verify the installation of the back-to-back water closets complies with Section 706.3, IPC 2006 with regard to the fittings.
11/02/2012 ROBERT SHERRY WATER REVIEW Approved
11/02/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM06961
5545 E Broadway #119

1. Provide 2006 IECC Budget Lighting calculation for the interior, ComCheck ok.
2.Provide a load for the Main Service which includes the load for this space.
3. Indicate on electrical plans where the main service located.

Ray T Majuta
Electrical Plan Review
PDSD, C of Tuc
11/2/2012
Ray.majuta@tucsonaz.gov
11/16/2012 CPIERCE1 WWM REVIEW Needs Review
11/16/2012 CPIERCE1 FIRE REVIEW Needs Review