Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM06886
Parcel: 12709016A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06886
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/30/2012 TERRY STEVENS ZONING REVIEW Approved
11/05/2012 KEN BROUILLETTE FIRE REVIEW Approved
11/08/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A-0; PROJECT INFORMATION: ADD THE ICC/ANSI A117.1-2003 ACCESSIBILITY CODE TO THE DRAWING.
2. SHEET A-1; KEYNOTES: NOTE 3 WAS NOT FOUND ON THE PLAN. VERIFY.
3. SHEET A-1; KEYNOTES: A NOTE INDICATES THE ELECTRIC WATER HEATER IS SUPPORTED ON A 72" HIGH SHELF. PROVIDE A REFERENCE FOR THAT SHELF DETAIL (A-1.2).
4. SHEET A-1; FLOOR PLAN: NO HIGH/LOW DRINKING FOUNTAIN OR SINGLE POINT OF USE WATER DISPENSER WAS LOCATED ON THE PLAN. VERIFY.
5. SHEET A-1; FLOOR PLAN: NO SERVICE SINK WAS LOCATED ON THE PLAN. VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/16/2012 ROBERT SHERRY WATER REVIEW Approved
11/16/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Verify the maintenance access requirements for the plaster trap (i.e. "Provide 3" between bottom of bottle and the cabinet base."). According to the manufacturer, the specified plaster trap (solids interceptor), the unit requires a bit more than 10" for removal of the screen; no clearance is required at the bottom of the interceptor. Reference: Section 310.4, UPC 2006.
2. Verify that the washer box installation includes a vent: provide a vent for each fixture trap. Reference: Sections 901.0 and 910.1, UPC 2006.
3. Revise waste and vent diagram "D". The plaster trap will function as the trap for the sink; no more than one trap shall be installed on a trap arm. Reference: Section 1001.1, UPC 2006.
4. The architectural keynotes on sheet A-1 call for a point-of-use water dispenser; where is it located?
11/19/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Correct the keynote for EF-3 on sheet M1.1.
2. Revise the mechanical design as required to avoid using the corridor as a return air duct. Reference: Section 601.2, IMC 2006.
3. Show the installation of a smoke detector in the return air duct of the existing air conditioner, upstream of any filters or outside air connections. Reference: Section 606.1, IMC 2006.
12/03/2012 GERRY KOZIOL WWM REVIEW Denied 1: PACIFIC DENTAL SERVICES (3RD OF 4 SUITES IN SHELL BUILDING, OTHER IS MATTRESS FIRM - PT12S01731 & VITAMIN SHOP- PT12S01788)
2: NEED TO SHOW SIZE & LOCATION OF ALL WATER METERS ON THE PROPERTY FOR SEWER CONNECTION FEE CALCULATION

Final Status

Task End Date Reviewer's Name Type of Review Description
12/06/2012 CPIERCE1 REJECT SHELF Completed
12/03/2012 CPIERCE1 OUT TO CUSTOMER Completed