Review Date Reviewer's Name Type of Review Description Status Comments
02/26/2013 MARTIN BROWN FIRE REVIEW Approved
03/04/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied 1. There are no written descriptions or comments for all the structural changes.
2. There are no structural calculations for the revisions made on sheets S2-02, S2-03, S3-01 and S4-01.
3. Structural calculations were submitted for the structural changes made at the CHVI Reception/Waiting however there are no structural plan and detail sheets showing the structural changes made.
a. Sheet A4-01M is not included in the revision submittal. This is the area where structural changes are made in the Reception/Waiting area.
END OF REVIEW
03/14/2013 LEERAY HANLY MECHANICAL-COMMERCIAL REVIEW Approved
03/14/2013 LEERAY HANLY ELECTRICAL-COMMERCIAL REVIEW Approved
03/14/2013 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
03/14/2013 FERNE RODRIGUEZ OUT TO CUSTOMER Completed