Permit Number: T12CM06790
Parcel: 12710084B

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06790
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET A1.1; DEMO PLAN: KEYNOTE 5 WAS NOT LOCATED ON THE PLAN. PROVIDE.
2. SHEET A1.1; DOCK PLAN: AT THE UPPER TRENCH DRAIN LOCATION, CLEAR UP THE DIMENSIONS, SLOPE, AND NOTES.
3. SHEET A1.1; DOCK PLAN: A 2'-0" DIMENSION AT THE BOTTOM OF THE LOWER TRENCH DRAIN SHOULD BE REPOSITIONED.
4. SHEET A1.1 (FLOOR PLAN KEYNOTES); SHEET A1.2 (SECTION 1): THE SECTION INDICATES A 1'-8" WIDE TRENCH, WHILE KEYNOTE 8 ON SHEET A1.1 INDICATES A 2'-0" WIDE TRENCH. CLARIFY.
5. SHEET A1.2; SECTION 1: ON THE 2X2X1/4 ANGLE, PROVIDE THE REBAR ANCHOR LENGTH AND SPACING.
6. SHEET A2.1; BUILDING SECTION 'A': FOR KEYNOTE 5 (NEW CMU WALL ON EXISTING PLANTER), PROVIDE A DETAIL FOR THE CONNECTION OF THE PLANTER WALL TO THE NEW WALL.
7. GENERAL: PROVIDE CONCRETE AND REINFORCING MATERIAL SPECIFICATIONS ON THE DRAWINGS.
8. GENERAL: PROVIDE DETAILS ON THE DRAWINGS FOR THE VARIOUS WALL SYSTEMS (NEW) CONNECTIONS TO THE EXISTING CONSTRUCTION.
9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/24/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/24/2012 ERIC NEWCOMB ADA REVIEW Passed
10/25/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/25/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Show how the new trench is to drain.
2. Show how overflow protection is being provided for the existing roof.
10/25/2012 ROBERT SHERRY WATER REVIEW Approved
10/25/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Passed
11/28/2012 CPIERCE1 WWM REVIEW Needs Review
11/28/2012 CPIERCE1 ZONING REVIEW Needs Review
11/28/2012 CPIERCE1 ENGINEERING REVIEW Needs Review
11/28/2012 CPIERCE1 FIRE REVIEW Needs Review