Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06790
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/24/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET A1.1; DEMO PLAN: KEYNOTE 5 WAS NOT LOCATED ON THE PLAN. PROVIDE. 2. SHEET A1.1; DOCK PLAN: AT THE UPPER TRENCH DRAIN LOCATION, CLEAR UP THE DIMENSIONS, SLOPE, AND NOTES. 3. SHEET A1.1; DOCK PLAN: A 2'-0" DIMENSION AT THE BOTTOM OF THE LOWER TRENCH DRAIN SHOULD BE REPOSITIONED. 4. SHEET A1.1 (FLOOR PLAN KEYNOTES); SHEET A1.2 (SECTION 1): THE SECTION INDICATES A 1'-8" WIDE TRENCH, WHILE KEYNOTE 8 ON SHEET A1.1 INDICATES A 2'-0" WIDE TRENCH. CLARIFY. 5. SHEET A1.2; SECTION 1: ON THE 2X2X1/4 ANGLE, PROVIDE THE REBAR ANCHOR LENGTH AND SPACING. 6. SHEET A2.1; BUILDING SECTION 'A': FOR KEYNOTE 5 (NEW CMU WALL ON EXISTING PLANTER), PROVIDE A DETAIL FOR THE CONNECTION OF THE PLANTER WALL TO THE NEW WALL. 7. GENERAL: PROVIDE CONCRETE AND REINFORCING MATERIAL SPECIFICATIONS ON THE DRAWINGS. 8. GENERAL: PROVIDE DETAILS ON THE DRAWINGS FOR THE VARIOUS WALL SYSTEMS (NEW) CONNECTIONS TO THE EXISTING CONSTRUCTION. 9. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/24/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/24/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/25/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/25/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Show how the new trench is to drain. 2. Show how overflow protection is being provided for the existing roof. |
| 10/25/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/25/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Passed | |
| 11/28/2012 | CPIERCE1 | WWM | REVIEW | Needs Review | |
| 11/28/2012 | CPIERCE1 | ZONING | REVIEW | Needs Review | |
| 11/28/2012 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 11/28/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review |