Permit Number: T12CM06722
Parcel: 12709016A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06722
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/13/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/13/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. The specified water heater has a bottom inlet for the cold water and will require the installation of a vacuum relief valve. Verify that installation of the vacuum relief valve for the water heater on the hot water pipe complies with the manufacturer's installation instructions. [Original comment: Verify that installation of the vacuum relief valve for the water heater on the hot water pipe complies with the manufacturer's installation instructions. Reference: Sections 501.0 and 504.2, IPC 2006.]
2. Verify the size of the threaded rod shown in detail 1/P2 - 3/8" or ½"?
11/13/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/13/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
11/16/2012 CPIERCE1 WWM REVIEW Needs Review