Permit Number: T12CM06711
Parcel: 12606204A

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06711
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/06/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET D1; KEY NOTES: NOTE D6.6 WAS NOT LOCATED ON THE PLAN. VERIFY.
2. SHEET D1; KEY NOTES: NOTE D9.1 WAS NOT LOCATED ON THE PLAN. VERIFY.
3. SHEET D1; KEY NOTES: NOTE D9.3 WAS SHOWN ON THE PLAN (SOUTH RESTROOM NEAR THE STAIR), BUT THIS NOTE IS NOT IN THE KEY NOTES. VERIFY.
4. SHEET D1; KEY NOTES: NOTE D16.3 WAS SHOWN ON THE PLAN (SOUTH WALL), BUT THIS NOTE IS NOT IN THE KEY NOTES. VERIFY.
5. SHEET D1.1; KEY NOTES: NOTE D9.7 WAS NOT LOCATED ON THE PLAN. VERIFY.
6. SHEET D1.1; KEY NOTES: NOTE D15.5 WAS NOT LOCATED ON THE PLAN. VERIFY.
7. SHEET D1.1; KEY NOTES: NOTE D15.7 WAS NOT LOCATED ON THE PLAN. VERIFY.
8. SHEET D1.1; KEY NOTES: NOTE D16.3 WAS NOT LOCATED ON THE PLAN. VERIFY.
9. SHEET A1; WALL DETAIL: DETAILS 2 AND 4 INDICATE WALL BRACING WHEN THE WALL IS PARALLEL TO THE FRAMING ABOVE. PROVIDE A DETAIL FOR THE CASE OF THE WALL PERPENDICULAR TO THE FRAMING (ADDED MEMBERS BETWEEN EXISTING FRAMING).
10. SHEET A1; FLOOR PLAN: DOORS TO THE JANITOR, ELECTRIC, AND PHONE ROOMS REDUCE THE HALL WIDTH BY OVER HALF. VERIFY IBC SECTION 1021.2 IS MET.
11. SHEET A1; FLOOR PLAN: A WALL ELEVATION MARK AT THE EAST WALL OF THE FRACTURE ROOM INDICATES --/A6. REVISE.
12. SHEET A1; KEY NOTES: NOTES 16.3, 16.4, AND 16.5 WERE SHOWN ON THE PLAN, BUT NOT IN THE KEY NOTES. CLARIFY.
13. SHEET A1; KEY NOTES: NOTES 6.4, 6.6, 6.8, 6.9, 6.11, 6.13, 9.1, 9.2, 9.3, 9.4, 9.5, 10.1, 10.5, 10.13, 10.17, AND 15.4 WERE NOT LOCATED ON THE PLAN (OR ON A2 PLAN). VERIFY.
14. SHEET A1; KEY NOTES: NOTE 9.2 INDICATES AN INCOMPLETE DETAIL. REVISE REFERENCE.
15. SHEET A1; KEY NOTES: NOTE 10.1 REFERENCES AN ADA GUIDELINE FOR AN ACCESSIBLE SIGN. REVISE THE REFERENCE TO THE ICC/ANSI A117.1-2003, FIGURE 703.3.10.
16. SHEET A1; KEY NOTES: NOTES 10.3 THROUGH 10.8 REFERENCE DETAILS ON SHEET A5. REVISE THE REFERENCE.
17. SHEET A3.1; DETAIL 9: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE.
18. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/09/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/21/2012 ROBERT SHERRY WATER REVIEW Approved
11/21/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
11/21/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
12/03/2012 GERRY KOZIOL WWM REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
12/03/2012 CPIERCE1 OUT TO CUSTOMER Completed
12/03/2012 CPIERCE1 REJECT SHELF Completed