Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06697
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/19/2012 | ENEWCOM1 | ENGINEERING | REVIEW | Approved | |
| 10/19/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/19/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET INDEX; CODE INFORMATION: REVIEW THE OCCUPANCY TYPE AND OCCUPANCY LOAD. 2. SHEET A0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WATER CLOSET/LAVATORY ELEVATIONS. 3. SHEET A0; WATER CLOSET ELEVATION: ADD THE DISTANCE FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF THE PAPER DISPENSER PER THE ICC/ANSI A117.1 FIGURE 604.7. 4. SHEET A1; NOTES AND EQUIPMENT PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES. 5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/19/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/23/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Passed | |
| 10/23/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide upper terminal cleanouts for the clothes washer and P-6. Reference: Section 707.4, UPC 2006. 2. Provide a cleanout for the mop sink. Reference: Section 707.4, UPC 2006. 3. Provide an expansion tank and a vacuum relief valve for the elevated water heater. 4. Verify that the 3" trap for P-6 is not oversized for the intended use (condensate drain). 5. Provide an indirect waste for the sanitizing compartment of P-10. 6. Correct the size of the pipe entering the grease interceptor - it is shown as 2" on the plumbing floor plan and 3" on the riser diagram. |
| 10/23/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/23/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 10/23/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 11/06/2012 | SPOWELL1 | WWM | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/06/2012 | SHANAE POWELL | OUT TO CUSTOMER | Completed |