Permit Number: T12CM06697
Parcel: 10321342A

Address:
2118 W GRANT RD

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06697
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2012 TERRY STEVENS ZONING REVIEW Approved
10/19/2012 ENEWCOM1 ENGINEERING REVIEW Approved
10/19/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/19/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET INDEX; CODE INFORMATION: REVIEW THE OCCUPANCY TYPE AND OCCUPANCY LOAD.
2. SHEET A0: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE WATER CLOSET/LAVATORY ELEVATIONS.
3. SHEET A0; WATER CLOSET ELEVATION: ADD THE DISTANCE FROM THE FRONT OF THE WATER CLOSET TO THE CENTERLINE OF THE PAPER DISPENSER PER THE ICC/ANSI A117.1 FIGURE 604.7.
4. SHEET A1; NOTES AND EQUIPMENT PLAN: THE CITY OF TUCSON REQUIRES ALL LETTERING (UPPER AND LOWER CASE) TO BE A MINIMUM OF 3/32" IN HEIGHT. REVISE THE NOTES.
5. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
10/19/2012 ERIC NEWCOMB ADA REVIEW Passed
10/23/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Passed
10/23/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide upper terminal cleanouts for the clothes washer and P-6. Reference: Section 707.4, UPC 2006.
2. Provide a cleanout for the mop sink. Reference: Section 707.4, UPC 2006.
3. Provide an expansion tank and a vacuum relief valve for the elevated water heater.
4. Verify that the 3" trap for P-6 is not oversized for the intended use (condensate drain).
5. Provide an indirect waste for the sanitizing compartment of P-10.
6. Correct the size of the pipe entering the grease interceptor - it is shown as 2" on the plumbing floor plan and 3" on the riser diagram.
10/23/2012 ROBERT SHERRY WATER REVIEW Approved
10/23/2012 KEN BROUILLETTE FIRE REVIEW Approved
10/23/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
11/06/2012 SPOWELL1 WWM REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/06/2012 SHANAE POWELL OUT TO CUSTOMER Completed