Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM06689
Parcel: 13401002D

Review Status: Completed

Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG

Permit Number - T12CM06689
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/19/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM06689

1. The generator is required to be grounded per 2005 NEC 250.30. There is no information on the Automatic Transfer Switches. How will systen be grounded under activation of generator?
2. The 125 amp breaker on the generator feeds the ATS then a feeder with #3's (100 amps), must increase feeder or lower breaker size ?
3.The 225 amp Breaker on the generator feeds the ATS then a feeder with 3/0's(200 amps), also Panel PCWIN1(200 amp rated panel and main) ?
4. This system qualifies as an Optional Standby System per 2005 NEC 702 and requires signs per 702.8,A and B, indicate on plan.
5. Where is City of Tucson panel fed from ?

Ray T Majuta
Elect Plan Review
PDSD, C of Tuc
10/19/2012
Ray.Majuta@tucsonaz.gov
11/07/2012 CPIERCE1 BUILDING-COMMERCIAL REVIEW Needs Review
11/07/2012 CPIERCE1 MECHANICAL-COMMERCIAL REVIEW Needs Review
11/07/2012 CPIERCE1 ENGINEERING REVIEW Needs Review
11/07/2012 BETH GRANT COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Needs Review
11/07/2012 CPIERCE1 FIRE REVIEW Needs Review
11/07/2012 CPIERCE1 ZONING REVIEW Needs Review

Final Status

Task End Date Reviewer's Name Type of Review Description
11/07/2012 CPIERCE1 OUT TO CUSTOMER Completed