| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/19/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM06689 1. The generator is required to be grounded per 2005 NEC 250.30. There is no information on the Automatic Transfer Switches. How will systen be grounded under activation of generator? 2. The 125 amp breaker on the generator feeds the ATS then a feeder with #3's (100 amps), must increase feeder or lower breaker size ? 3.The 225 amp Breaker on the generator feeds the ATS then a feeder with 3/0's(200 amps), also Panel PCWIN1(200 amp rated panel and main) ? 4. This system qualifies as an Optional Standby System per 2005 NEC 702 and requires signs per 702.8,A and B, indicate on plan. 5. Where is City of Tucson panel fed from ? Ray T Majuta Elect Plan Review PDSD, C of Tuc 10/19/2012 Ray.Majuta@tucsonaz.gov |
| 11/07/2012 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/07/2012 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/07/2012 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 11/07/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/07/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 11/07/2012 | CPIERCE1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |