Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM06687
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/22/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM06687 1. Existing Panel CPLA, where is this panel fed from ? 2. How will the generator be grounded concerning the neutral? 3.Will the new ATS showing it is a 3 pole have a solid neutral connection, and if the panels that the generator feeds are from different services, how will the grounded system be affected ? 4. If generator is classified under 2005 NEC 702, indicate signs are to be installed per 702.8, A and B. 5. Are Panels CPLA and CPLB rated 150amps ? Ray T Majuta Elect Plan Review PDSD, C of Tuc 10/19/2012 Ray.Majuta@tucsonaz.gov |
| 11/07/2012 | CPIERCE1 | BUILDING-COMMERCIAL | REVIEW | Needs Review | |
| 11/07/2012 | CPIERCE1 | MECHANICAL-COMMERCIAL | REVIEW | Needs Review | |
| 11/07/2012 | CPIERCE1 | ENGINEERING | REVIEW | Needs Review | |
| 11/07/2012 | BETH GRANT | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Needs Review | |
| 11/07/2012 | CPIERCE1 | FIRE | REVIEW | Needs Review | |
| 11/07/2012 | CPIERCE1 | ZONING | REVIEW | Needs Review |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 11/07/2012 | CPIERCE1 | OUT TO CUSTOMER | Completed |