Permit Number: T12CM06677
Parcel: 10503032C

Address:
5061 N ORACLE RD

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06677
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
01/24/2013 RONALD BROWN BUILDING-COMMERCIAL REVIEW Denied SHEET LS-1
1. New code calculated occupancy load increases the water closets required for women to three. Use of the actual numbers of 314 still comes out to a fraction higher than 2 for the water closets. Please file an appeal with the building official, Mr. Ron Boose to utilize the reduced occupancy load shown as actual and a round off from 2.09 w.c. to 2.0.
2. Flag pole foundation detail 1A/6.1 does not corrlate with structural calculations and details. Please reconcile.
END OF REVIEW
02/27/2013 FRODRIG2 ELECTRICAL-COMMERCIAL REVIEW Needs Review