Permit Number: T12CM06560
Parcel: 13317064C

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06560
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/24/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide structural calculations and a detail to show how the proposed water heater platforms are to be safely supported from the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006.
2. Show how the termination point for each of the T&P relief valves complies with Section 504.6 (2), IPC 2006.
10/24/2012 ROBERT SHERRY WATER REVIEW Denied The water pressure calculations indicate that a 2" water meter and a 3" RPBP are supplying the water service to this suite but it is not clear that the meter serves only this suite. Show that the installation of the new plumbing fixtures will not cause the existing water supply system to become overloaded. Reference: Section 102.4, IPC 2006.
10/24/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/25/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/26/2012 MARTIN BROWN FIRE REVIEW Approved
11/02/2012 GERRY KOZIOL WWM REVIEW Approved