| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/24/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide structural calculations and a detail to show how the proposed water heater platforms are to be safely supported from the building structure. Reference: Sections 106.3.1 and 301.2, IPC 2006. 2. Show how the termination point for each of the T&P relief valves complies with Section 504.6 (2), IPC 2006. |
| 10/24/2012 | ROBERT SHERRY | WATER | REVIEW | Denied | The water pressure calculations indicate that a 2" water meter and a 3" RPBP are supplying the water service to this suite but it is not clear that the meter serves only this suite. Show that the installation of the new plumbing fixtures will not cause the existing water supply system to become overloaded. Reference: Section 102.4, IPC 2006. |
| 10/24/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/25/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/26/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 11/02/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |