Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM06550
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 01/14/2013 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 01/22/2013 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. "Stainless steel" by itself is not a material standard. All plumbing fixtures shall be third-party listed. [Original comment: Provide material standards (e.g. NSF) for all plumbing fixtures being provided by others. Reference: Section 303.4, IPC 2006.] 2. The waste and vent diagram now shows the 3-compartment sink with two traps on a single trap arm. Reference: Section 911.2, IPC 2006. [Original comment: Provide an indirect connection for the sanitizing compartment of the 3-compartment sink with a direct waste connection for the wash and rinse sections of the 3-compartment sink. Reference: Section 802.1, IPC 2006.] |
| 01/23/2013 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Denied | 1. The revised ventilation calculations are incorrect. See Sections 403.3 and 403.3.2, IMC 2006 for instructions regarding the determination of the required outside air quantities. [Original comment: Correct the outside air calculations. Reference: Section 106.3.1, IMC 2006.] 2. The wall located behind the hood is still constructed with combustible supports; provide the required clearance between the hood and the wall. In addition, the stainless steel sheet material is supposed to be located "…between the hood and the gypsum wallboard over an area extending not less than 18 inches (457 mm) in all directions beyond the hood." [Original comment: Note 1.11 on sheet indicates that the walls behind the proposed hood are of frame construction. Per Section 507.9, IMC 2006, this construction does not qualify as non-combustible due to the wood studs. Show how the hood installation will be revised to comply with the requirements of Section 507.9, IMC 2006 for clearances.] 3. If the proposed Type I hood is listed per UL 710, the required airflow rate will be determined by the manufacturer; an unlisted wall-mounted canopy hood over a heavy-duty cooking appliance has a required exhaust flow rate of 400 CFM per foot of length. Reference: Section 507.13.2, IMC 2006. [Original comment: Coordinate the required exhaust flow rate for the Type I hood as shown in the Exhaust Hood Schedule with the Exhaust Hood Calculations and the Exhaust Fan Schedule. (Note that the statement, "Factory-built commercial exhaust hoods which are tested in accordance with UL 710…do not have to comply with 507" is only partially correct.) Reference: Sections 106.3.1 and 507.1, exception 1, IMC 2006.] 4. The revised mechanical plan shows supply air being delivered to each restroom but the exhaust fans are still controlled by the restroom light switches. Revise the operation of the exhaust fans so that all air introduced into each restroom will be exhausted (i.e. the exhaust fans shall operate whenever HVAC air is supplied to the restrooms). Reference: Section 403.2.1 (4), IMC 2006. 5. The revised mechanical plan shows high velocity diffusers for the room air conditioning system in close proximity to the face of the Type I hoods. Verify that the location and type of air conditioning diffusers complies with the hood manufacturer's installation instructions. High velocity air streams in close proximity to the face of the hood can lead to the hood failing the capture and containment test. Reference: Sections 304.1 and 507.16.1, IMC 2006. 6. Provide structural calculations to verify that the existing roof is capable of supporting the additional dead load due to the installation of the roof top unit, EF-1. The existing roof is not part of the structural calculation package. Reference: Section 302.1, IMC 2006. 7. Provide structural details to show how the new fan coil unit is to be connected to the building structure. Reference: Section 302.1, IMC 2006. 8. Show how adequate access (for maintenance or unit removal) is being provided for the new fan coil unit located above the ceiling. Reference: Section 306.3, IMC 2006. 9. Show the size, routing, and termination of the condensate drain for FC-1. Reference: Section 307.2, IMC 2006 as amended by the City of Tucson. 10. Provide an auxiliary drain pan or a secondary drain system for the fan coil unit. Reference: Section 307.2.3 IMC 2006. |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 01/29/2013 | FERNE RODRIGUEZ | OUT TO CUSTOMER | Completed |
| 01/29/2013 | CPIERCE1 | REJECT SHELF | Completed |