Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: T12CM06550
Parcel: 13014019K

Address:
4602 E 29TH ST

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06550
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. SHEET CS; AREA CALCULATIONS; LOT COVERAGE CALCULATION: UNDER 'AREA CALCULATIONS', THE TOTAL INTERIOR AREA IS LISTED AS 781 SF, WHILE THE 'LOT COVERAGE CALCULATION' LISTS THE RESTAURANT AS 856 SF. COORDINATE.
2. SHEET A1; FLOOR PLAN: PER THE 2006 IBC, TABLE 2902.1, A RESTAURANT REQUIRES SEPARATE MALE AND FEMALE RESTROOMS (SEPARATE FACILITIES REQUIRED PER SECTION 2902.2). PROVIDE.
3. SHEET A1; FLOOR PLAN: A SERVICE SINK, AS REQUIRED BY THE IBC TABLE 2902.1, WAS NOT LOCATED ON THE PLAN. PROVIDE.
4. SHEET A1; KEYNOTES 1.4 AND 1.5: PROVIDE THE WALL STUD SPACING IN THE NOTES.
5. SHEET A1 (FLOOR PLAN); KEYNOTES: KEYNOTES 1.12 AND 1.13 WERE NOT LOCATED ON THIS PLAN. REFERENCE ON THE PLANS SHEET A2 FOR ADDITIONAL NOTE LOCATIONS.
6. SHEET A1 (REFLECTED CEILING PLAN); KEYNOTES: KEYNOTE 4.4 WAS NOT LOCATED ON THIS PLAN. REFERENCE ON THE PLANS SHEET A2 FOR ADDITIONAL NOTE LOCATIONS.
7. SHEET A1; KEYNOTES: ADD A NOTE ON SHEETS A1 AND A2 INDICATING THAT ALL KEYNOTES MAY NOT BE ON ONE SHEET.
8. SHEET A3; ROOF PLAN: KEYNOTE 2 INDICATES 3 NEW EVAPORATIVE COOLERS ON THE EXISTING ROOF. PROVIDE STRUCTURAL CALCULATIONS THAT SHOW THE EXISTING ROOF JOISTS ARE CAPABLE OF CARRYING THE NEW LOADS.
9. GENERAL: IS THE 447 SF PORCH A NEW ADDITION, OR IS IT EXISTING AND THE PORCH COVER IS NEW? PROPERTY RESEARCH ONLINE INDICATES THERE IS NO EXISTING PORCH. VERIFY.
10. SHEET S1: NO STRUCTURAL CALCULATIONS WERE SUBMITTED FOR THE NEW PORCH COVER AND FOUNDATION. PROVIDE.
11. SHEET S1: PROVIDE STRUCTURAL GENERAL NOTES (INCLUDING MATERIAL STRENGTHS AND DESIGN LOADS) ON THIS SHEET.
12. SHEET S1; WOOD BEAM/HEADER SCHEDULE: PROVIDE MAXIMUM SPAN LENGTHS IN THE SCHEDULE FOR B1 AND B2.
13. SHEET S1; WOOD BEAM/HEADER SCHEDULE: A NOTE INDICATES BEAMS B1 AND B2 ARE SIZED PER IBC TABLE 2308.9.5. THERE IS NO BEAM INDICATED IN THAT TABLE FOR 3-2X6 OR FOR 6X8. VERIFY.
14. SHEET S1; DETAIL 6: INDICATE FOOTING DEPTHS (CONTINUOUS FOOTING AND COLUMN FOOTING) ON THE DETAIL.
15. SHEET S1: PROVIDE A DETAIL OF THE CONTINUOUS FOOTING AT THE NEW PORCH.
16. SHEET S1; DETAIL 6: INDICATE FOOTING REINFORCEMENT AT THE FOOTINGS.
17. SHEET S1; DETAIL 6: INDICATE THE FINISH EXTERIOR GRADE ON THE DETAIL.
18. SHEET S1; DETAIL 1: NOTE 6 INDICATES TO SEE THE PLAN FOR THE STUD SIZE. PROVIDE.
19. SHEET S1; DETAIL 2: REMOVE THE COLUMN NOTE FOR A 4X4 POST. THERE ARE NONE INDICATED ON THIS JOB.
20. SHEET S1; DETAIL 3: KEYNOTE 8 IS MISSING. PROVIDE.
21. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/29/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Approved
12/10/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Clarify the plumbing code to be used for this activity. Notes on sheet P1.1 refer to both the 2006 IPC and to the 2006 UPC. This review has been made using the 2006 IPC.
2. Verify the size of the existing water meter - until very recently, Tucson Water has installed 5/8" meters, not ¾" meters.
3. Provide material standards (e.g. NSF) for all plumbing fixtures being provided by others. Reference: Section 303.4, IPC 2006.
4. Provide an indirect connection for the sanitizing compartment of the 3-compartment sink with a direct waste connection for the wash and rinse sections of the 3-compartment sink. Reference: Section 802.1, IPC 2006.
5. Equipment (e.g. evaporative coolers) discharging non-potable clear-water waste to the building drainage system shall discharge to an indirect waste receptor via an air gap or an air break. Reference: Section 802.1.5, IPC 2006.
6. Show how the flow control device can be installed below the floor level with ready access (defined as being able "to be directly reached without requiring the removal or movement of any panel, door or similar obstruction") and in accordance with the manufacturer's instructions. Reference: Sections 202 and 1003.3.5, IPC 2006.
7. Provide sizing information for the roof scuppers. Reference: Sections 1106 and 1107.3, IPC 2006.
12/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied 1. Correct the outside air calculations. Reference: Section 106.3.1, IMC 2006.
2. Show how the specified unit heaters are capable of maintaining a minimum temperature of 68 F in the interior spaces intended for occupancy on a design heating day (32 F). Reference: Sections 309.1 and 312.1, IMC 2006.
3. Note 1.11 on sheet indicates that the walls behind the proposed hood are of frame construction. Per Section 507.9, IMC 2006, this construction does not qualify as non-combustible due to the wood studs. Show how the hood installation will be revised to comply with the requirements of Section 507.9, IMC 2006 for clearances.
4. Coordinate the required exhaust flow rate for the Type I hood as shown in the Exhaust Hood Schedule with the Exhaust Hood Calculations and the Exhaust Fan Schedule. (Note that the statement, "Factory-built commercial exhaust hoods which are tested in accordance with UL 710…do not have to comply with 507" is only partially correct.) Reference: Sections 106.3.1 and 507.1, exception 1, IMC 2006.