Permit Number: T12CM06545
Parcel: 115020130

Address:
509 E WAVERLY ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM06545
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/16/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 11-16-12
Activity: T12CM06545 2nd review
Address: 509 E Waverly St
Applicant: Robert Otero

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

STRUCTURAL / FRAMING PLAN:
2. Clarify the intent of matching the existing 4x6 roof framing design if the rafters will be concealed with a sheet rock ceiling.
3. Correct section detail references over bedroom #1, bedroom #4, and bathroom #2 - sheet 5 framing plan.
4. Clarify the location of all parapets (new and existing).

ELECTRICAL PLAN:
10. Remove garage from the panel schedule or specify the location of the garage.

INTERNATIONAL ENERGY CONSERVATION CODE:
11. Clarify insulation method. Framing plans call for 6x framing members. Fiberglass insulation is over 9 inches tall for the minimum R-30 in ceiling cavities.
12. Demonstrate energy compliance for walls and ceiling in bedroom #1.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review