Permit Number - T12CM06545
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/29/2012 GERRY KOZIOL WWM REVIEW Approved
10/29/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Denied PLAN REVIEW COMMENTS
Date: 10-29-12
Activity: T12CM06545
Address: 509 E Waverly St
Applicant: Robert Otero

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

SITE PLAN:
1. Correct misspelling of street name on plot plan.

STRUCTURAL / FRAMING PLAN:
2. Clarify the intent of matching the existing 4x6 roof framing design if the rafters will be concealed with a sheet rock ceiling.
3. Correct section detail references over bedroom #1, bedroom #4, and bathroom #2 - sheet 5 framing plan.
4. Clarify the location of all parapets (new and existing).

SECTIONS - DETAILS:
5. Specify the depth of footings below grade - detail 5 sheet 4.

PLUMBING PLAN:
6. Provide a water meter and a water supply line for the proposed demand. Note: Tucson Water limits the design capacity of 5/8" water meters to 11 fixture units.

ELECTRICAL PLAN:
7. Show locations of smoke detectors in every sleeping room and hallways leading to. All smoke detectors must be interconnected with a power source from the building wiring, and shall be equipped with battery backup. When ceiling finish materials are not removed, existing bedrooms may be equipped with battery operated smoke detectors, R313.
8. Bedroom outlets shall be protected with combination-type arc-fault breakers including smoke detectors, E3802.12.
9. Correct the location of the water heater disconnect to coincide with floor plan layout.
10. Remove garage from the panel schedule or specify the location of the garage.

INTERNATIONAL ENERGY CONSERVATION CODE:
11. Clarify insulation method. Framing plans call for 6x framing members. Fiberglass insulation is over 9 inches tall for the minimum R-30 in ceiling cavities.
12. Demonstrate energy compliance for walls and ceiling in bedroom #1.