Permit Number - T12CM06513
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/02/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Denied 1. GENERAL; STRUCTURAL DRAWINGS: THE DRAWINGS INDICATE FIVE STRUCTURAL SHEETS, BUT ONLY FOUR ARE PROVIDED. CLARIFY.
2. GENERAL; STRUCTURAL DRAWINGS (SHEETS 2 AND 3 OF 5): PROVIDE A NOTE ON THESE SHEETS THAT ALL OF THE PARTS LISTED MAY NOT BE ON THAT SPECIFIC SHEET.
3. GENERAL: STRUCTURAL DRAWINGS (SHEET 3 OF 5): ADD PARTS 9 AND 10 TO THE LIST SINCE THEY DO APPEAR ON THIS SHEET.
4. GENERAL; STRUCTURAL CALCULATIONS (PAGE 10): THE UPPER TABLE INDICATES 3-3/4" DIAMETER ANCHORS IN THE CONCRETE. WHERE ARE THESE SHOWN ON THE DRAWINGS?
5. GENERAL; SHEETS T1.0, A1.0, AND A1.1: THESE SHEETS ARE NOT STAMPED, SIGNED, AND DATED BY A REGISTERED DESIGN PROFESSIONAL AS REQUIRED BY THE 2006 IBC, SECTION 106. VERIFY.
6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS.
11/02/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved

Final Status

Task End Date Reviewer's Name Type of Review Description
11/08/2012 SHANAE POWELL OUT TO CUSTOMER Completed
11/08/2012 SHANAE POWELL REJECT SHELF Completed