Review Details: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Permit Number - T12CM06513
Review Name: COMMERCIAL - BLDG/FIRE/ZONING/ENG
Review Status: Completed
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
11/02/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. GENERAL; STRUCTURAL DRAWINGS: THE DRAWINGS INDICATE FIVE STRUCTURAL SHEETS, BUT ONLY FOUR ARE PROVIDED. CLARIFY. 2. GENERAL; STRUCTURAL DRAWINGS (SHEETS 2 AND 3 OF 5): PROVIDE A NOTE ON THESE SHEETS THAT ALL OF THE PARTS LISTED MAY NOT BE ON THAT SPECIFIC SHEET. 3. GENERAL: STRUCTURAL DRAWINGS (SHEET 3 OF 5): ADD PARTS 9 AND 10 TO THE LIST SINCE THEY DO APPEAR ON THIS SHEET. 4. GENERAL; STRUCTURAL CALCULATIONS (PAGE 10): THE UPPER TABLE INDICATES 3-3/4" DIAMETER ANCHORS IN THE CONCRETE. WHERE ARE THESE SHOWN ON THE DRAWINGS? 5. GENERAL; SHEETS T1.0, A1.0, AND A1.1: THESE SHEETS ARE NOT STAMPED, SIGNED, AND DATED BY A REGISTERED DESIGN PROFESSIONAL AS REQUIRED BY THE 2006 IBC, SECTION 106. VERIFY. 6. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
11/02/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved |
Final Status
Task End Date | Reviewer's Name | Type of Review | Description |
---|---|---|---|
11/08/2012 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
11/08/2012 | SHANAE POWELL | REJECT SHELF | Completed |