Permit Number: T12CM06502
Parcel: 108160070

Address:
4810 N 1ST AV

Review Status: Completed

Review Details: RESUBMITTAL - TI ALL

Permit Number - T12CM06502
Review Name: RESUBMITTAL - TI ALL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/26/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
11/29/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Denied T12CM06502

1. Last review dated 10/23/12 requested a calculation showing compliance with City of Tucson Outdoor lighting Code Ord # 10963. This calculation includes all outdoor fixtures on site and on the building. The submitted Exterior
Lighting Compliance Report is different than what is required. The Outdoor Lighting Code for Tucson can be found on the City of Tucson Web site. By going to Departments, then Development Services, then Building Codes ( on the Left bar). Any questions please call
520-837-4988 , 8 AM to 3:30 PM.

Ray T Majuta
Elect Plan Review
PDSD, City of Tucson
11/30/2012
Ray.Majuta@tucsonaz.gov.
11/30/2012 TERRY STEVENS ZONING REVIEW Denied Zoning cannot approve the building plans until the development package has been approved.
12/06/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Denied Provide a structural detail showing how the Type I hoods are to be supported from the building structure. Coordinate the mechanical notes regarding the hood supports with the structural notes (e.g. the mechanical notes call for ¾" threaded rods but the roof framing drawing calls for 3/8" threaded rods). [Original comment: Provide structural calculations and details to show that the Type I and Type II hoods are supported from the building structure in accordance with Section 507.6, IMC 2006. Reference: Section 302.1, IMC 2006.]
12/06/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Approved
12/12/2012 GERRY KOZIOL WWM REVIEW Denied 1: CULVER'S RESTAURANT
2: NEED TO SHOW SIZE AND LOCATION OF ALL WATER METERS ON DRAWINGS FOR SEWER CONNECTION FEE CALCULATIONS
3: NEED PCRWRD/3RD FLOOR/CAPACITY EVALUATION -KURT STEMM- 740-6534
4: NEED SITE UTILITY PLAN SHOWING LOCATION/METHOD OF CONNECTION TO PUBLIC SEWER - CHAD AMATEAU - 740-6547