Permit Number: T12CM06432
Parcel: 138040830

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM06432
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
08/02/2013 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Reqs Change PLAN REVIEW COMMENTS
Date: 8-05-13
Activity: T12CM06432
Address: 951 W. Calle Lerdo
Applicant: Leonard Gonzales

This letter reflects comments to be addressed. The purpose of this review is to verify compliance to the 2012 International Residential Code with local amendments. In order to facilitate a shorter back check time, we request that you please provide two complete sets of revised plans and calculations, along with a written response to each of the noted items indicating action taken. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. The City of Tucson has adopted the 2012 International family of codes. As of 1/01/2013 all code references should refer to the currently adopted code or appeal must be made to the Building Official for alternate code use on electrical drawing.
2. Bonding note on electrical riser diagram should not point to the grounding icon. Grounding and bonding are both required, E3607/8
3. Show full batt insulation over the new exterior wall that meets the minimum prescriptive value, N1102.1.
4. Show the location of the proposed post under the new glulam beams, R801.2.

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
08/08/2013 CPIERCE1 REJECT SHELF Completed