Permit Review Detail
Review Status: Completed
Review Details: RESUBMITTAL
Permit Number - T12CM06385
Review Name: RESUBMITTAL
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2012 | KEN BROUILLETTE | FIRE | REVIEW | Approved | |
| 10/22/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Denied | 1. SHEET PV1.0; SOLAR CANOPY PLAN AND PROFILE: THE PLAN LAYOUT INDICATES A HORIZONTAL DIMENSION OF 34'-8 3/8", WHILE THE PROFILE INDICATES 34'-8 1/2". COORDINATE. 2. SHEET PV1.0; SOLAR CANOPY PLAN: A NOTE TO THE LEFT OF THE PLAN INDICATES THE "PREFERRED LOCATION FOR STEEL POSTS-DIMENSIONS ARE APPROXIMATE". REMOVE THIS NOTE (STRUCTURAL SHEET 1 OF 4 INDICATES DIMENSIONS). 3. SHEET 2 OF 4; STRUCTURAL CALCULATIONS (PAGE 9): THE CALCULATIONS INDICATE A W14X34 COLUMN SECTION, BUT THIS COLUMN SIZE WAS NOT LOCATED ON THE DRAWINGS. VERIFY AND ADD TO DRAWINGS. 4. SHEET 2 OF 4 (DETAIL 2); STRUCTURAL CALCULATIONS (PAGE 15): THE CALCULATIONS INDICATE THE COLUMN CONNECTION PLATES (EACH SIDE OF COLUMN) TO BE 5/8" X 7" X 12", WHILE THE DETAIL INDICATES 5/8" X 7" X 0'-10" (THE CALCULATION ON PAGE 16 INDICATES 5/8" X 7" X 0'-10"). COORDINATE. 5. SHEET 2 OF 4 (DETAIL 2); STRUCTURAL CALCULATIONS (PAGE 15): THE CALCULATIONS INDICATE THE SHEAR PLATE TO BE CONNECTED TO THE COLUMN WITH 1/4" WELD ALL AROUND, WHILE THE DETAIL INDICATES 3/16" WELD. COORDINATE. 6. SHEET 2 OF 4; SECTION 1: A REFERENCE AT THE UPPER RIGHT SIDE OF THIS SECTION REFERENCES DETAIL 3/3 FOR THE PANEL CONNECTION. REVISE THAT REFERENCE. 7. SHEET 2 OF 4; DETAIL 3: PROVIDE A DETAIL (OR USE DETAIL 2/3) TO SHOW THE BOTTOM PLATE OF THE W14X30 BEAM AND ITS CONNECTION TO THE W14X30 WEB (DETAIL 2/3 INDICATES A FULL DEPTH W14X30). 8. SHEET 3 OF 4 (DETAIL 1); STRUCTURAL CALCULATIONS (PAGE 13): THE CALCULATIONS INDICATE THE 'SCHLETTER MID-CLIP FOR THE PANELS TO THE PURLINS SHOULD HAVE (2) 1/4" DIAMETER TEK SCREWS, WHILE THE DETAIL INDICATES (2) #12 SCREWS. COORDINATE. 9. STRUCTURAL CALCULATIONS; PAGE 17: WHERE IS THIS BOLTED CONNECTION INDICATED ON THE DRAWINGS? VERIFY. 10. GENERAL: PROVIDE WRITTEN RESPONSES TO ALL REVIEW COMMENTS. |
| 10/24/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Denied | T12CM06385 6565 E Broadway Photovoltaic System 1. Concerning System #1, line side tap, provide a detail cut sheet showing how the entry of the conduit and conductors will be allowed enough room for bending radius required . Also indicte type of terminals the lugs are to be terminated on. Will the terminations need to be drilled for attatchment of new lugs ?.Indicate the size of the existing bus way . Concerning the System #2 line side tap, provide the same information as for System #1. These type of installations require more information on the plan in order to prevent confusion between inspectors and installers. Ray T Majuta PDSD, City of Tucson Elect Plan Review 10/26/2012 Ray.Majuta@tucsonaz.gov |
Final Status
| Task End Date | Reviewer's Name | Type of Review | Description |
|---|---|---|---|
| 10/30/2012 | SHANAE POWELL | OUT TO CUSTOMER | Completed |
| 10/30/2012 | SHANAE POWELL | REJECT SHELF | Completed |