Permit Review Detail
Review Status: Completed
Review Details: COMMERCIAL - TI
Permit Number - T12CM06369
Review Name: COMMERCIAL - TI
Review Status: Completed
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/10/2012 | TERRY STEVENS | ZONING | REVIEW | Approved | |
| 10/10/2012 | ROBERT SHERRY | MECHANICAL-COMMERCIAL | REVIEW | Approved | |
| 10/10/2012 | RAY MAJUTA | ELECTRICAL-COMMERCIAL | REVIEW | Approved | |
| 10/10/2012 | ROBERT SHERRY | WATER | REVIEW | Approved | |
| 10/10/2012 | ERIC NEWCOMB | BUILDING-COMMERCIAL | REVIEW | Approved | |
| 10/10/2012 | LOREN MAKUS | ENGINEERING | REVIEW | Approved | |
| 10/10/2012 | ROBERT SHERRY | PLUMBING-COMMERCIAL | REVIEW | Denied | 1. Provide a detail showing how the water heater platform is connected to the building structure and the size of the all-thread hangers. 2. Show that the installation of the water heater and it's supporting platform comply with the requirements of Section 602.2.1, IMC 2006 (materials exposed within plenums). 3. Clarify detail4/MP2 with respect to the cold water inlet and the connection of the expansion tank. The specified water heater has a low, side inlet, not a top inlet. |
| 10/10/2012 | ERIC NEWCOMB | ADA | REVIEW | Passed | |
| 10/10/2012 | ERIC NEWCOMB | COMMERCIAL IMPACT FEE | COMMERCIAL IMPACT FEE PROCESSING | Passed | |
| 10/11/2012 | MARTIN BROWN | FIRE | REVIEW | Approved | |
| 10/15/2012 | GERRY KOZIOL | WWM | REVIEW | Approved |