Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Permit Number: T12CM06367
Parcel: 133231460

Review Status: Completed

Review Details: COMMERCIAL - TI

Permit Number - T12CM06367
Review Name: COMMERCIAL - TI
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/10/2012 TERRY STEVENS ZONING REVIEW Approved
10/10/2012 ROBERT SHERRY MECHANICAL-COMMERCIAL REVIEW Approved
10/10/2012 RAY MAJUTA ELECTRICAL-COMMERCIAL REVIEW Approved
10/10/2012 ROBERT SHERRY WATER REVIEW Approved
10/10/2012 ERIC NEWCOMB BUILDING-COMMERCIAL REVIEW Approved
10/10/2012 LOREN MAKUS ENGINEERING REVIEW Approved
10/10/2012 ROBERT SHERRY PLUMBING-COMMERCIAL REVIEW Denied 1. Provide a detail showing how the water heater platform is connected to the building structure and the size of the all-thread hangers.
2. Show that the installation of the water heater and it's supporting platform comply with the requirements of Section 602.2.1, IMC 2006 (materials exposed within plenums).
3. Clarify detail4/MP2 with respect to the cold water inlet and the connection of the expansion tank. The specified water heater has a low, side inlet, not a top inlet.
10/10/2012 CARL SCHULTZ FIRE REVIEW Approved
10/10/2012 ERIC NEWCOMB COMMERCIAL IMPACT FEE COMMERCIAL IMPACT FEE PROCESSING Passed
10/10/2012 ERIC NEWCOMB ADA REVIEW Passed
10/15/2012 GERRY KOZIOL WWM REVIEW Approved