Permit Number: T12CM06327
Parcel: 11206407A

Address:
2207 E COPPER ST

Review Status: Completed

Review Details: RESIDENTIAL - BLDG/WWM

Permit Number - T12CM06327
Review Name: RESIDENTIAL - BLDG/WWM
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
10/22/2012 GERRY KOZIOL WWM REVIEW Approved
11/09/2012 CLAYTON TREVILLYAN BUILDING-RESIDENTIAL REVIEW Approved PLAN REVIEW COMMENTS
Date: 11-09-12
Activity: T12CM06327
Address: 2207 E Copper St
Applicant: Benjamin Design

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. In order to facilitate a shorter back check time, we request that you please provide revised plans and calculations, along with a written response to each of the noted items indicating action taken.

SCOPE OF REVIEW:
The scope of this plan review includes architectural, electrical, plumbing, mechanical, and energy conservation. The purpose of this review is to verify compliance to the 2006 International Residential Code with local amendments. Other comment references may be derived from additional codes and standards adopted by The City of Tucson. All features have been checked only to the extent allowed by the submittals provided for review. All portions of this project are assumed to meet other departmental requirements, conditions, and concerns before permit approval.

GENERAL REQUIREMENTS:
1. Clarify section references on sheet A2 to correspond with the correct sheet number.
2. Note that light fixtures in clothes closets shall be installed in accordance with E3903.11.

PLUMBING PLAN:
3. The UPC code has been specified for use in the design of the plumbing system and IRC values have been used. Clarify
4. Tucson water limits the demand of 5/8" water meters below the requested flow. Specify a ¾" water meter or larger for the

If you have any questions please contact:
Clayton Trevillyan
520.837.4913
Residential Plan Review

Final Status

Task End Date Reviewer's Name Type of Review Description
01/07/2013 SHANAE POWELL OUT TO CUSTOMER Completed