Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

The login landing page when selecting 'View' is still occurring and is still pending further investigation. 

Permit Number: T12CM06292
Parcel: 11302037F

Address:
1050 E EASY ST

Review Status: Completed

Review Details: RESUBMITTAL

Permit Number - T12CM06292
Review Name: RESUBMITTAL
Review Status: Completed
Review Date Reviewer's Name Type of Review Description Status Comments
11/29/2012 MICHAEL ST. PAUL ZONING REVIEW Denied CDRC TRANSMITTAL


FROM: Michael St.Paul, Planning Technician

PROJECT:
T12CM06292
1050 East Easy Street
New Single Family Residence (SFR)


TRANSMITTAL: November 29, 2012


COMMENTS: Please attach a response letter with the next submittal, which states how all Zoning Review Section comments regarding the Land Use Code and Development Standards were addressed.


This site is located in the R-2 zone (LUC Section 2.3.5.2.A.1). The Development Designator is "I" (LUC Sections 2.3.5.2.A.1 & 3.2.3.1.B) and the Perimeter Yard Indicator is AA (LUC Sections 3.2.3.1.B & 3.2.6.4).

Revise the dimension for the building heights on the plot plans. The setback heights are measured from design grand (ground level) to the highest point of each wall (LUC Sections 3.2.6.4 & 3.2.7.2.B). The dimensions provided are from finished floor.

Revise the elevations. The east and west elevation provided are the mirror image of what is on the plot plans.

See lot split (S07-142), on the plot plan.
12/04/2012 KEN VAN KARSEN BUILDING-RESIDENTIAL REVIEW Approved
12/10/2012 GERRY KOZIOL WWM REVIEW Denied 1: NEED PCRWRD/1ST FLOOR REVIEW OF INGRESS/EGRESS/UTILITY FOR PRIVATE SEWER RUNNING THRU 1048 E EASY ST (DKT & PG, OR SEQUENCE #?)

Final Status

Task End Date Reviewer's Name Type of Review Description
12/10/2012 CINDY AGUILAR OUT TO CUSTOMER Completed
12/10/2012 CPIERCE1 REJECT SHELF Completed